Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Where can I find trip curves for the QO-GFI, QO-EPD, and QO-EPE breakers?
Issue:
Where can I find trip curves for the QO/B-GFI, QO/B-EPD and QO/B-EPE breakers?

Product Line:
QO/B-GFI, QO/B-EPD and QO/B-EPE 1P, 2P and 3P Miniature Circuit Breakers

Resolution:
Use the Class 910 trip curves for QO/B-GFI breakers. Though EPD and EPE breakers are not listed on the curve, their trip characteristic is identical to the QO/B-GFI. These curves also apply to the 3P versions of the breakers as well, even though they are not listed on the curve.
Use 910-1 for 15A 1P https://www.se.com/us/en/download/document/910-1/
Use 910-2 for 20A 1P https://www.se.com/us/en/download/document/910-2/
Use 910-3 for 15, 20 and 25A 2P and 3P and 25A 1P https://www.se.com/us/en/download/document/910-3/
Use 910-4 for 30A 1P, 2P and 3P https://www.se.com/us/en/download/document/910-4/
Use 910-5 for 40 to 60A 2P, 40 to 50A 3P https://www.se.com/us/en/download/document/910-5/

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings