Trying to replace a 10 foot section of AP510 busway. The busway is obsolete, so what can I use?
Issue:
AP510 busway 10ft replacement section.

Product Line:
I-Line Busway

Environment:
Products sold in North America

Resolution:
You can replace the old busway section with an 8 foot section of new plug-in busway and two, one foot adapters. Catalog numbers are: AF2510G12S for the slot adapter and AF2510G12B is the bolt side adapter. AP2510G8ST is the 8ft plug-in straight piece that goes between them.

It is recommended to use the AT2 assembly tool and HF53F hangers.