How is the range and differential set on a 9016GAW1 ?<br /><br />
The range adjustment sets the decreasing set point and must be set first . To increase operating points ; place a flat bladed screwdriver in the slots of the range adjustment nut and rotate from left to right . An independent adjustment of the set point on increasing pressure is next by turning the differential screw counter clockwise to raise the setpoint on increasing vacuum .