Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Does the ATS48 have ground fault protection?

Issue:
Is ground fault protection provide by the ATS48?

Product Line:
ATS48

Resolution:
The ALTISTART48 soft start Y-range product design meets the requirements of the North American market. The soft starter provides ground fault protection through the use of three current transformers to meet equipment level protection, limiting damage to conductors and equipment on the load side of the protective element per NEC/NFPA 70, Article 230.95.
The method of ground fault detection considers the measured sum of three phase currents and signals are compared to the scaled setting of the current limitation of soft starter. The level of detection is fixed based on ground fault current (phase-to-ground) level of 25% of the product ICL rating. In such an event, the soft starter will fault in ``OLF`` mode provided the ground fault current is present for a minimum of 100ms.
Updates to published documentation are forthcoming. If additional information is required, please contact your local Square D / Schneider Electric Field sales representative.

***

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings