Is an additional neutral lug or equipment ground lug, available for use when a QO2150, QO2175 or QO2200 branch circuit breaker, or QO2225SL sub-feed lug kit is used in a QO single-phase load center?
Issue:
Product accessories

Product Line:
Homeline load centers

Cause:
Application

Resolution:

A neutral lug kit, LK225AN, is provided with these branch circuit breakers, for field installation on the load centers neutral bar. In most applications, a standard equipment ground bar will be able to terminate the circuit's equipment ground conductor. If an additional equipment ground lug may be required, order LK100AN separately, for field installation on a standard equipment ground bar.
NOTE: These breakers can be applied only in Square D SINGLE PHASE QO load centers. DO NOT USE IN Square D THREE PHASE QO load centers or other manufacturers' load centers or panelboards. See the Instruction Sheet provided with the circuit breaker or sub-feed lug kit for further mounting restrictions that may apply regarding mounting these devices or adjacent branch circuit breakers.


Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings