Can auxiliary contacts be field installed on a NEMA 7 & 9 safety switch?
Issue:
What is the field installable auxiliary contacts for NEMA 7/9 enclosed switch?

Product Line:
Heavy Duty Safety Switch

Resolution:
An auxiliary switch for field installation is not available. A factory installed auxiliary switch can be provided with suffix 1212 for 1a/1b or suffix 1352 for 2a/2b.

NOTE: The enclosed molded case switch could be replaced with one that includes the aux switch.