Can the QO, 3-phase main lug ONLY (or FIXED main lug) load centers be converted to a main breaker load center?

Article available in these languages: Spanish

Issue:
Product Design Features

Product Line:
QO 3phase Load Center

Resolution:
ALL of the QO, 3phase Main lug load centers are considered FIXED Main Lug and CANNOT  be converted to a standard Main Breaker.


NOTE: the only option would be to back feed a branch breaker on the interior, BUT the branch breaker is limited to 100amp MAX and a retaining bracket kit is required. The branch breaker will require 3 pole spaces on the interior. ALWAYS FOLLOW WHAT THE National Electrical Code REQUIRES FOR BACK FEEDING AND SERVICE ENTRANCE.
1) If the Load Center will NOT be used as a Service Entrance panel the retaining kit part number is PK3MB.
2) If the load center will be used as a Service Entrance Panel the retaining kit part number is PKSB3BF.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings