Are NF panels rated for use on 600Y/347V systems?
Issue:
Can the EDB breakers in a NF panels be used on 600Y/347V systems?

Product Line:
NF Panelboards

Environment:
Application

Cause:
Clarification

Resolution:
Yes, The NF panel and EDB breakers can be used for the 600V/347V Wye voltage system, as long as the 600v version of the EDB breaker is used, for example, p/n EDB36015.
This is contrast to the 480/Y277V rated EDB34015 breaker.