How do we order an illuminated flashing pushbutton in the XB4/XB5 22mm push pushbutton product lines?
Issue:
How do we order an illuminated flashing 22mm push button?

Product Line:
22mm Push Buttons

Environment:
XB4/ XB5 Pilot lights

Cause:
Application is calling for flashing lights.

Resolution:
1.Order illuminated operator.
2.Oder one of the following flashing light module: Part number for flahsing protected LED: for 24VAC flashing is ZB4BV18B* for 110V flashing is ZB4BV18G*. * add suffix (1-White, 3 -Green, 4 - Red, 5-Yellow, 6-Blue
3. Add-On contact blocks ZBE101 or ZBE102