Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Do PowerPacT MG and MJ type breakers have a test port on the trip unit for secondary injection testing?
Issue:
Does MG and MJ type breakers have a test port on the trip unit for secondary injection testing?

Product Line:
Legacy Breaker

Resolution:
The PowerPacT M frame breakers have a perforated label over the test port. The perforation can be removed for access to the port. If the FFTK has the 1.10 version firmware or higher, it can be used to test the trip unit.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings