Can I use Square D Class 5230 trench duct installed on a plant floor that is going to be hosed down once a week?
Issue:
Square D Class 5230 trench duct able to be hosed down once a week

Product Line:
Wire Management

Environment:
Factory

Cause:
Product Features

Resolution:
This duct is gasketed. It will be water resistant but not water proof. The intent of the gasketing was to protect from incidental water such as a spilt bucket of water.
Hose down rating is not a feature that this product is rated for.