Could the obsolete Integral starter be used for single phase applications?
Issue:
Checking if the integral starters could be used for single phase applications.

Product Line:
Integral Starters

Environment:
Obsolete products

Resolution:
Due to single phase sensitivity of the protection modules, Integral Starters are designed for three phase applications. However, the overload module does not monitor phase angles. In a single phase application, the customer can wire 2 poles in series for one side of the load with the other side of the load returning thru the remaining pole.