Can a 6.0P or 6.0H trip unit be used for ground fault alarm only, without tripping?
Issue:
Ground fault alarm only is required, not ground fault trip.

Product Line:
Molded Case Circuit Breakers

Resolution:
No, the Micrologic 6.0P and 6.0H trip units cannot be used for ground fault alarm only. These trip units have both ground fault alarm AND trip.
If a breaker is required with ground fault alarm only, then use the Micrologic 5.0P or 5.0H trip unit.