Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the maximum voltage rating for a QO and Homeline load centers and branch breakers?

Article available in these languages: Spanish

Issue:
Product design features

Product Line;
QO Load Centers

Resolution:
The maxumum voltage rating for the QO and Homeline load centers and branch breakers is 240 Vac MAX.

NOTE:

1) Homeline does NOT have any DC voltage ratings

2) For 125V DC Voltage ratings of QO Load Centers see the FAQ - FA95999 (Link = https://www.se.com/us/en/faqs/FA95999/)

3) For 48V DC Voltage ratings of QO Breakers see the FAQ - FA120732 (Link = https://www.se.com/us/en/faqs/FA120732/)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings