Does SquareD/Schneider Electric make a 3 phase Transformer with a neutral on the primary input side?

Issue:
Most three phase Transformers have Delta primaries, with no neutral

Product Line:
LV Transformers

Environment:
Applies to LV Transformers by SquareD/Schneider Electric

Cause:
Delta Primaries are inherently more stable

Resolution:

SquareD/Schneider Electric provides Wye primary on Delta secondary with center tap Transformers (T151 voltage code). The primary of this unit does not provide a terminal for a neutral. Connecting the primary of a Transformer to the neutral point of a Wye system can cause troublesome neutral currents during times of imbalance.  Generally,  it is best to select a Delta primary for most 3 phase applications, even when connecting to a Wye power system. Other custom Wye primary Transformers may also be available for Solar and Alternative Energy applications.  Inquire about these with your local SquareD/Schneider Electric Distributors and Field Offices.



Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings