What is the difference between K-13 (Type NLP) and K-4 (Type NL) rated Transformers?

Article available in these languages: Spanish

Issue:
Many loads used in Industrial and Commercial applications can generate harmonic energy which may be harmful to standard Transformers

Product Line:
LV Transformers

Environment:
Applies to Ventilated type Transformers by SquareD/Schneider Electric

Cause:
K rated Transformers are available as a possible solution to the problem of harmonic energy that might damage a standard Transformer


Resolution:

K-Factor is a measure of current distortion in the load fed by a Transformer. The higher the number, the greater the capacity of the Transformer to handle high levels of continuous single-phase, line-to-neutral non-linear loads. Square D/Schneider Electric recommends K-4 rated Transformers for computer and other similar loads found in commercial and industrial systems for duty cycles (24 hour average loading) of 80-95%. If the duty cycle is expected to exceed 95%, then K-13 would be needed. For duty cycles up to 50%, use Type EE energy efficient Transformers. For duty cycles of 50-80%, use Watchdog Low Temperature Rise Transformers.
The need for K-Factor rated Transformers is currently in question because standard, general purpose Transformers can supply typical commercial and industrial `non-linear` loads up to more than 80% of nameplate rating without overheating. Studies have shown that typical loading of low voltage dry Type transformers is less than 35% as a daily average.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings