Is there a GFI option for the breakers used in the NF panelboards? (EDB, EGB, EJB)

Article available in these languages: Spanish

Issue:
GFI option for the breakers used in the NF panelboards (EDB, EGB, EJB).

Product Line:
NF Panelboards, E Frame Circuit Breaker

Environment:
Products sold in North America


Resolution:
No, the EDB, EGB, and EJB circuit breakers do not come with a GFI option for people protection at 4-6mA.  They are only available with equipment ground-fault protection at 30mA (EPD).  These are only available in single-pole.

Note: NF EPD circuit breakers cannot be used on phase to ground less then 277V. These breakers are not suitable for a 208Y/120V application.

18 ka @480Y/277 Vac35 ka @480Y/277 Vac65 ka @480Y/277 Vac
15 AEDB14015EPDEGB14015EPDEJB14015EPD
20 AEDB14020EPDEGB14020EPDEJB14020EPD
30 AEDB14030EPDEGB14030EPDEJB14030EPD
40 AEDB14040EPDEGB14040EPDEJB14040EPD
50 AEDB14050EPDEGB14050EPDEJB14050EPD

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings