Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What type of cable is used for connecting medium voltage switchgear to transformers?
Issue:
Sizing the cable for a medium voltage  product.

Product Line:
Medium voltage switchgear and transformers

Environment:
Installation

Cause:
N/A

Resolution:
The transformer manufacturer uses either 7.5kV or 15kV insulated non-shielded cable. Either 1 or 2 #2/0 Cables per phase depending on the line current. Since the cable in non-shielded, air clearances are maintained.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings