What is the power supply requirement for Micrologic trip units for Powerpact P and R frames and Masterpact breakers?
Issue:
What is the power supply requirement for Micrologic trip units for Powerpact P, R and Masterpact breakers?

Product Line:
Powerpact and Masterpact

Resolution:
The power requirement for all Micrologic trip units for Powerpact P and R frames and Masterpact breakers is 50 mA @ 24 Vdc ±5%, max ripple 1%. Use terminals F2 (+) and F1(-).
Picture showing the wiring diagram of the trip units
For help with Micrologic trip units and modbus communications for Masterpact and Powerpact P and R circuit breakers, consult instruction manuals:
Powerpact P, R, and Masterpact NW, NT Micrologic™ types 2.0, 3.0 and 5.0 Trip Units, see 48049-207-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Trip Units, see 48049-136-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0P and 6.0P Trip Units, see 48049-137-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0H and 6.0H Trip Units, see 48049-330-03

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings