Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can The RM4TR32 unit be used on a 480V nominal system?
Issue:
Using the RM4TR32 Phase Failure Relay on a 480V nominal system

Product Line:
RM4 Zelio Phase Measurement Relays

Environment:
Zelio Phase Measurement Relays

Resolution:
No. RM4TR32 will not work on 480V systems. It will always be tripped on overvoltage. RM4TR32 is obsolete.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings