What are some appropriate steps to troubleshoot an inoperative transformer?
Issue:
How to troubleshoot a Dry type EE or EX transformer?

Product Line:
transformer

Environment:
EE and EX transformers

Cause:
trouble shooting incorrect voltages, wiring issues, odd or weird voltages to ground, or inoperative transformer

Resolution:
1. Check that line and load connections are properly made and that appropriate jumpers and/or tap settings are in accord with nameplate instructions.
2. Measure input voltage to insure that voltage is within 5% of nominal rated voltage or tap setting
3. If input circuit protection opens while energizing transformer, make sure fuse or circuit breaker is a minimum 1.25 x full load input current rating of the transformer.
4. If the transformer can be energized, measure output voltage with no load on transformer to insure that voltage is within tolerance.
5. If a neutral is derived on the load side of the transformer, insure that neutral ground bonding is accomplished in accord with National Electric Code or local code requirements. Failure to ground neutrals is often the cause of unusual voltage measurements to ground.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings