Issue:
When selecting branch breakers for the mini powerzone MPZB devices, Do you select the 25K or 65K AIC rated breakers?
Product Line:
Mini Powerzone
Environment:
MPZ MPZB
Resolution:
No. The 25K or 65K AIC is for the main breaker only. The secondary branch breakers can be the standard 10,000 AIC breakers.
When selecting branch breakers for the mini powerzone MPZB devices, Do you select the 25K or 65K AIC rated breakers?
Product Line:
Mini Powerzone
Environment:
MPZ MPZB
Resolution:
No. The 25K or 65K AIC is for the main breaker only. The secondary branch breakers can be the standard 10,000 AIC breakers.