What medium voltage fuses come standard with blown fuse indication?
Issue:
Can Medium voltage fuses have Blown Fuse indication?

Product Line:
Medium Voltage Metal Enclosed Switchgear

Environment:
Application

Cause:
Product Features

Resolution:
All current limiting fuses have pop up pins that indicate when the fuse has blown. S&C boric acid fuses have a red/green blown fuse indicator as standard. Cutler Hammer boric acid fuses do not have the indicator as standard, but it can be ordered as an option. These indicators are visual only and don't have any contacts available for signaling.