What is the catalog number for a sensor plug for a Powerpact P, R, or Masterpact NW, NT breaker?
Issue:
Need Sensor plug catalog number

Product Line:
Circuit Breakers

Resolution:
Note: See 2nd table for Masterpact Y frame (6p) replacement sensor plugs.
Pic of sensor plug

Sensor Plugs for PowerPact P, R, and Masterpact NW, NT
Rating
(Amps)
Part #
100(*)S47051
250(*)S47052
400S47053
600S48823
630S33091
800
S33092
1000S33093
1200S48824
1250S33094
1600S33095
2000S33982
2500S33983
3000S48825
3200S33984
4000(IEC and ANSI) S47820
* Cannot be installed into a circuit breaker with original sensor plug higher
than 250 A. Likewise, a circuit breaker with original sensor plug of 100 A or
250 A cannot be replaced with a sensor plug higher than 250 A.

Masterpact Y Frame (6p) Sensor Plugs
Rating
(Amps)
Part #
2000S47821
2500S47822
3000S48826
3200S47823
4000S47824
5000S47825
6000S48827
6300S47826

Installation Notes:
Masterpact NT and NW:  Sensor plugs are field installable down to 50% of the FRAME rating.
Example:  Masterpact with a 1600 A frame can receive sensor plugs from 800-1600 A.

Powerpact P and R:  Sensor plugs are field installable down to 50% of the CURRENT rating.
Example: Powerpact P frame breaker with 800 A sensor installed at the factory can only receive sensors from 400-800 A.

For complete details on installing sensor plugs and their restrictions, please see instruction bulletin 48049-145-03.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings