Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the fuses in the IMA or IBA MA modules be replaced?

Issue:
Can the fuses in the IMA or IBA MA modules be replaced?

Product Line:
Surge Protective Devices (SPDs)

Environment:
Maintenance

Cause:
Replacement

Resolution:
There are no replaceable fuses in the IMA or IBA MA modules. These modules use thermally protected MOVs. If either LED on an MA module is not lit, the module should be replaced. If both green LEDs are not lit and the diagnostic display panel has power, it indicates a loss of power to that phase or the module needs replacement. If the correct voltage is present on that phase, the MA module will need to be replaced.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings