Is it possible to install more than one surge protector into a panel?

Issue:
Is it possible to install more than one surge protector into a panel?

Product Line:
TVSS Surge Suppression

Environment:
Application, installation

Cause:
The user desires a higher peak surge current rating.

Resolution:
Yes, multiple SPDs can be added to the same panel. Essentially, the SPDs are connected in parallel, which increases the total peak surge current rating for the panel. The surge current will be divided among all connected SPDs.