What tenant breakers do the EZM, 225amp Max. meter socket branch devices accept, both 3-Phase and 1-Phase?

Article available in these languages: Spanish

Issue:
Current product design

Product Line:
EZM Metering

Environment:
Tenant breakers

Cause:
Product features

Resolution:
The EZM 225amp meter socket branch devices will ONLY accept as standard, Type QBP-TM, QDP-TM, QGP-TM or QJP-TM circuit breakers from 70A minimum to 225A maximum. The 1phase IN-1phase OUT and the 3phase IN-1phase OUT devices will use 2pole tenant breakers and the 3phase IN-3phase OUT will use 3pole tenant breakers.

NOTE: There is a adapter kit that does allow for the use of a 2pole, QO tenant breaker to be used in the single phase ONLY 225amp meter socket branch devices, catalog number EZM125QOA, BUT see the current digest for a description and the Short Circuit Current Rating of the ENTIRE EZM-Line when this kit is used.


CTA-ID : 2042723

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings