What is the terminal lug data for an NQ, 400 amp main lugs interiors?
Issue:
What is the wire range for NQ430L4,NQ430L4C, NQ442L4, NQ442L4C, NQ454L4, NQ454L4C, NQ472L4, NQ472L4C, NQ484L4C?


Product Line:
NQ panelboards

Environment:
Installation

Resolution:
The lugs accept 1 - #1/0 to 750kcmil or 2 - 1/0 to 350kcmil Al/Cu per phase.