Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the lug torque specification for a Powerpact J frame circuit breaker?
Product Line:
Circuit Breakers

Resolution:
The standard Al/Cu lugs are rated at 225 lb-in and require a 5/16 in hex bit torque wrench. See below for lug information.
The AL175JD (150 - 175 A) is 225 lb - in.
The AL250JD (200 - 250 A) is 225 lb - in.
The CU250JD (150 - 250 A) is 250 lb - in

See instruction bulletin, 48940-221-02

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings