Can comb bus bars for Multi 9 C60BP circuit breakers be cut to any desired length?

Issue:
Cutting M9 UL recognized comb busbars for C60BP circuit breakers

Product Line:
UL 489 listed Multi 9

Environment:
Installation

Resolution:

  • "Standard" UL recognized busbars cannot be cut, but there are two lengths to choose from. For unused positions - use end cap M9XCTC15.
    • M9XUP106 M9XUP312 M9XUP312 M9XUP312 M9XUP312 M9R81425
  • "Cuttable" UL recognized busbars are also available.  For unused positions use end cap M9XCEC10.
    • M9XCP157 M9XCP256 M9XCP357 M9XCA137 M9XCA348

See graphic below for details.

IEC style comb bus bars are cuttable.  Use end caps M9XCEC10 on both ends.
Cuttable Comb Busbars