Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can ground fault be disabled on a Micrologic 6.0A, 6.0P, or 6.0H trip unit on a Masterpact NT/NW or PowerPacT P/R frame circuit breaker?
Issue:
Can the ground fault pickup be disabled on a Micrologic 6.0A (ammeter), 6.0P (power), or 6.0H (harmonic) trip unit?

Product Line:
Micrologic, Masterpact, Powerpact

Resolution:
No. To eliminate ground fault protection, replace the trip unit with a 5.0 of the same type.
For ground fault alarm, replace the trip unit with a 5.0P or 5.0H trip unit and use an M2C (S64273) programmable contact module or I/O module(s) (LV434063).

Note:  if ground needs to be temporarily disabled for primary injection testing, refer to FA98682.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings