How do you wire the shunt trip on a EDB breaker?

Product Line:
PowerPact E frame

Environment:
Applies to EDB, EGB, and EJB with shunt trip accessory installed.

Resolution:
Use terminals 6 & 7 on the breaker to wire the shunt trip. Because it is AC, it is polarity insensitive. The other terminals are not operative.

Illustration

For more information please see instruction bulletin 48840-097-02.