Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the largest branch breaker available in the 400A NQ panel in a NEMA 3R enclosure?
Issue:
What is the maximum amp of a branch breaker that can be installed in a 400A NQ panel in a weatherproof enclosure?

Product Line:
NQ Circuit Breaker panels sold and supported in the USA.

Environment:
Specifications

Cause:
Product Features

Resolution:
Due to heat rise restrictions inside the NEMA 3R enclosure, the maximum branch breaker is a 150A/3P QOB-VH branch. A 150A sub feed breaker is the largest subfeed branch that can be utilized.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings