What is the part number for a 200% neutral assembly for the J250S, J250F, J250R, J250DS, J250SS, and J250AWK circuit breaker enclosures?
Issue:
Product design featurs

Product Line:
Circuit Breaker Enclosure

Resolution:
For a 200% neutral application, use the solid neutral SN400LA and use copper wire ONLY.
The SN400LA will accept (1) #1 AWG - 600 kcmil or (2) #1 AWG - 250 Kcmil Al/Cu conductors IN and OUT.