What class of fuse do ALL the 60 A, 600Vac Max., heavy duty safety switches accept?

Issue:

Product design features

Product Line:
Heavy Duty Safety Switches

Environment:
Class of Fuses

Cause:
Application

Resolution:
HDSS = Heavy Duty Safety Switches
SCCR = Short Circuit Current Rating

ALL the 60amp, 600Vac max., HDSS accept Class H or K fuses as standard. Options include Class R fuses (field install Class R Fuse Kit) and Class J fuses (field relocate the fuse base assembly to alternate position marked in the enclosure). With Class H or K fuses installed, the switches are UL/CSA listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R fuses (and Class R Fuse Kit installed) or Class J fuses installed, the switches are UL/CSA listed for use on systems with up to 200,000 RMS Symmetrical Amperes available fault current.

NOTES:
1) All Square D Canadian 30 - 200amp, 600Vac, 3pole HDSS leave the factory to accept class J Fuses as standard(Including the Crouse Hinds Receptacle switches). Conversion to Class H fuses requires relocating the load side base assembly to an alternate position as marked in the enclosure.

2)
DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability and will void the warranty.

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings