HU1003MC5: Is there a replacement?
Issue:
What replaces the obsolete MCC disconnect HU1003MC5?

Product Line:
Model 5 Motor Control Centers

Environment:
Products sold in North America

Resolution:
The entire bucket will need to be replaced with a new Model 6 MCC bucket.  All  model 5 parts for old buckets including handles, linkages, saddle assemblies are all obsolete.  Make sure to request Model 6 bucket to fit Model 5 structure to obtain the correct midshelf to install into Model 5 structures.