Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the dimensions for the J250F and J250S circuit breaker enclosures?
Issue:
Dimensions

Product Line:
Circuit Breaker Enclosure

Resolution:
Both enclosures are 31.00" H x 14.00" W x 5.96" D.
The J250F flush cover is 32.50" H x 15.42" W.
The J250S surface cover is 31.43" H x 14.35" W.

See drawing at the following link: https://www.se.com/us/en/download/document/3362S/

The drawing is also attached.


Schneider Electric USA

Attachment(s)
3362S.pdf [98.23 KB]
Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings