Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the difference between the J250S and JD250S circuit breaker enclosures?
Issue:
Product Features

Product Line:
Circuit Breaker Enclosure

Resolution:
The JD250S is physically smaller than the J250S and has application limitations. The JD250S is UL listed only to accept an HDL or JDL 3 pole circuit breaker. The voltage is limited to 480 Vac maximum. The SCCR is limited to 18 kAIC at 240 Vac or 480 Vac. Copper conductors must be used.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings