What is the replacement for a QMB3640?

Issue:
Replacement for obsolete switch QMB3640

Product Line:
QMB panelboard, switchboard with QMB distribution.

Environment:
Products sold in North America

Resolution:
The replacement depends on the existing busbar design inside the QMB panel or Switchboard.  There are three designs, round, flat and railroad track like.

There is no longer a fusible switch replacement for a QMB3640, 400A QMB Series 4 switch for the QMB panel with round busbars.
However, if the panel has flat busbars, we do have a QMB3400LA circuit breaker unit and the QMB310EX plug-on extension assembly, is also required in order to mount the breaker unit.
If the panel has the railroad track looking busbars, the replacement would just be the QMB3400LA.

When replacing the QMB3640 you may need filler plates but they are obsolete, no longer available, with no replacement. Suggest installer to have fabrication done at a local sheet metal shop.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings