Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the replacement 120V coil for a LC1D115?
Issue:
Replacement  of 120V coil for a LC1D115

Product Line:
Tesys D

Environment:
IEC contactors and starters

Resolution:
The part number is LX1D8G7 for the dual frequency. LX1D8G6 for 60Hz only.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings