Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What size cable does a LAD7B10 accept?
Issue:
Need to know the size cable accepted by the LAD7B10 block.

Product Line:
TeSys D overload relays

Environment:
IEC Contactors and starters

Cause:
Identifying cabling requirements.

Resolution:
It takes either a 1 flexible cable without cable end size 14-8 AWG or 1 flex cable with cable end size 16-12AWG or 1 solid cable without cable end size 16-10 AWG.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings