Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Error When Attempting a Runtime Calibration in PowerChute Software

Issue:
Error When Attempting a Runtime Calibration in PowerChute Software

Product Line:
PowerChute Serial Shutdown
PowerChute Business Edition

Environment:
All supported OS

Cause:
1) The battery has less than 100% charge:
2) The load on the UPS is 10% or less:

Resolution:
Two conditions need to be met to perform a calibration:

1) The battery charge needs to be at 100%,
2) The load on the UPS needs to be greater than 10% of the battery capacity

Schneider Electric USA

Explore more
Range:
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings