Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What size conductors will the feed through lugs accommodate on a 600 amp, main breaker type NF panelboard?
Issue:
600 Amp wire size for main breaker NF Panelboards.

Product Line:
Panelboards

Environment:
NF Panelboards

Cause:
Wire size

Resolution:
The feed through lugs will accommodate (2) 1/0-750 kcmil

Schneider Electric USA