Does a shunt trip and close coil come automatically with a motor-operated Powerpact P frame breaker?
Issue:
Does a shunt trip and close coil come automatically with a motor-operated Powerpact P frame breaker?

Product Line:
Powerpact P frame circuit breakers

Environment:
Electrical Distribution Systems:

Cause:
Literature is not clear on whether or not these coils are included.

Resolution:
A shunt trip and close coil with the same voltage rating as the motor are included with a spring charging motor.  An SDE contact is also included.
It is possible to order a second shunt trip or an undervoltage release device of the same or a different voltage.
Three auxiliary switches OF may also be ordered, but an SD switch is not possible on this breaker.