Issue:
How to set R1 to control an isolation contactor in SoftStarter ATS48?

Product Line:
Variable Speed Drives and Soft Starters

Environment:
Soft Start - Altistart 48

Resolution:
From the display status screen, typically rdY or nLP, arrow down to the IO menu and ENT.  Arrow to parameter r1, ENT and change to R1I. ENT to save.