Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the operating temperature range of the ATS01 soft starters?
Issue:
What is ATS01 soft starter operating temperature?

Product Line:
ATS01

Environment:
All series

Causes:
N/A

Resolution:
The ATS01 soft starters are rated for use in ambient temperatures ranging from -10C (14F) to +40C (104F).  The starter can be used up to 50C (122F) by derating the current by 2% per degree C above 40C.

The obsolete ATS01N2**LY were rated for use in ambient temperatures ranging from 0C (32F) to +55C (131F).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings