Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I change the Profibus address on the ATV61 or ATV71 with an optional Profibus card?
Issue:
ATV61 or ATV71 change of the Profibus address with the optional Profibus card.

Product Line:
Altivar 61, Altivar 71

Environment:
Profibus network

Cause:
Configuration

Resolution:

Profibus card part numbers are VW3A3307 or VW3A3307S371.

The profibus address is set through a series of 8 dip switchs on the card beside the 9 pin profibus connector.  The address is set in binary form.  A switch in the up position indicates 0 and in the down position indicates 1.  The least significant bit is the far right switch. Example, to set the address to 36 (binary 00100100).  Place the switches in order from left to right: UP, UP, DOWN, UP, UP, DOWN, UP, UP.

Profibus option card photo 1

Refer to page 11 in either of the attached Profibus manuals for switch configurations. You can also download the manuals using these links:

ATV61/71 Profibus DP manual - VW3A3307
https://www.se.com/us/en/download/document/1755873/

ATV61/71 Profibus DPv1 manual - VW3A3307S371:
https://www.se.com/ww/en/download/document/AAV52935/

Schneider Electric USA

Attachment(s)
ATV6171 Profibus DP manual - VW3A3307 1755873.pdf [439.59 KB]
ATV61_71_PROFIBUS_DPv1_EN_AAV52935_02.pdf [597.24 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings