Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How is the ATV12 programmed for a 0-10Vdc analog input on AI1?
Issue:
Programming an ATV12 for a 0-10Vdc analog input on AI1

Product Line:
ATV12

Environment:
Programming

Cause:
n/a

Resolution:
The factory default is for a 0-5Vdc input.  Set AI1t = 10U to accommodate a 0-10V input.  AI1t is found in the IO menu and AI1 submenu.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings