How can the ATV212 or ATV21 be set up for start/stop on terminal and ramp to 60 Hz?

Resolution:
Begin by wiring the remote start switch or relay for two wire control between terminals P24 and F.

Program the nameplate motor parameters into the following parameters:

CODE - DESCRIPTION
thr - Motor thermal prot.
uLu - Motor rated voltage
F415 - Motor rated current
F417 - Motor rated speed


Make the following parameter settings:

CODE - DESCRIPTIONSETTING
LL - Low limit frequencyas desired
UL - Upper limit freq60
Dec - Deceleration ramp timeas desired
ACC - Acceleration ramp timeas desired
CMOD - Command mode selection0

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings