Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
When replacing and ATV66 with a ATV61/71, what are the control wiring considerations?
Issue:
Control wiring considerations when replacing an ATV66 with a ATV61/71

Product Line:
Altivar 66

Environment:
All releases

Cause:
Replacing drives.

Resolution:
When converting the wiring to the Altivar 61/71 drive, discard the wires on CL1 and CL2 (ATV66) , not used on the ATV61/71.
Also the run permissive and run forward are swapped around, between the ATV66 and ATV61/71.
ATV66:        LI1 = run permissive and LI2 = run forward
ATV61/71:   LI1 = run forward and LI2 = run permissive (nSt)  (run permissive, if used assign freewheel stop nSt (Fun Menu 1.7) to LI2))
Most other terminations will be the same.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings